Analys av värmesystem, förslag på effektiviseringar för att värma vatten/ballast för   modulära betongstationer
Umeå universitet, Teknisk-naturvetenskapliga fakulteten, Institutionen för tillämpad fysik och elektronik.
2011 (Svenska)Självständigt arbete på grundnivå (yrkesexamen), 10 poäng / 15 hpStudentuppsats (Examensarbete)Alternativ titel
Analysis of the heating system, proposals on how to make efficiency improvements to heat   water / ballast for modular concrete plants (Engelska)
Abstract [sv]

Denna rapport avhandlar möjligheterna att återvinna en del av den värme som används till att värma upp ballast i ballastfickor i samband med betongtillverkning då temperaturen utomhus är lägre än fem grader Celsius. Tre olika beräkningsfall med skiljda typer av uppvärmning redovisas. Alla beräkningar har gjorts vid en utomhustemperatur av 0 °C, för varierande utomhustemperaturer presenteras grafer i slutet av resultatkapitlet.

Fall 1, där ballasten värms med befuktade rökgaser har en ingående beräknad effekt av 506 kW, där 67,5 kW går att återvinna vilket gör att den procentuella andelen återvinningsbar effekt är 13,4 %. Vidare visar beräkningarna att den ingående temperaturen sjunker från 300 °C till 162 °C just ovanför ballasten. Tiden för uppvärmning av materialet blir i detta fall 5 minuter.

Fall 2, där ballasten värms med varm luft har en ingående beräknad effekt av 10 kW, där 7,6 kW går att återvinna, vilket gör att den procentuella andelen återvinningsbar effekt är 76,3 %. Vidare visar beräkningarna att den ingående temperaturen sjunker från 100 °C till 78 °C just ovanför ballasten. Tiden för uppvärmning av materialet blir i detta fall 16 timmar.

Fall 3, där ballasten värms med befuktad luft har en ingående effekt av 85,3 kW, där all effekt åtgår till att värma ballasten, driftsfallet visar sig arbeta med ett underskott av energi där ballasten skulle kunna absorbera en hel del mer effekt. Därför blir den procentuella andelen återvinningsbar energi 0 %, den ingående temperaturen sjunker från 100 °C till 0 °C just ovanför ballasten. Tiden för uppvärmning av materialet blir i detta fall 27 minuter.

Abstract [en]

In this thesis I examine the potential to recover some of the heat used to warm up ballast when the material is stored in ballast tanks, at an industrial sized concrete facility at outdoor temperatures below +5 °C. Three different cases with different heating applications are covered. All calculations has been made using 0 °C as outdoor temperature, results with varying outdoor temperature is shown in graphs at the end of the results chapter.

Case 1, where the ballast is heated with humidified flue gas has a calculated estimated output of 506 kW, of these 506 kW, 67.5 kW can be recycled, which means that the theoretical percentage of recyclable power is 13.4%. Furthermore, the calculations show that the inlet temperature drops from 300 °C to 162 °C just above the ballast. The time for heating the material is in this case 5 minutes.

Case 2, where the ballast is heated with dry hot air at a calculated estimated output of 10 kW, of these 10 kW, 7.6 kW can be recycled, which means that the theoretical percentage of recyclable power is 76.3%. Furthermore, the calculations show that the inlet temperature drops from 100 °C to 78 °C just above the ballast. The time for heating the material is in this case 16 hours.

Case 3, where the ballast is heated with humidified air has a calculated estimated output of 85.3 kW, where all power is used to heat the ballast. The case is shown to work with a deficit of energy which means the ballast could absorb a lot more power than is actually available. Therefore, the percentage of recoverable energy is 0 %, and consequently the inlet temperature drops from 100 °C to 0 °C

Ort, förlag, år, upplaga, sidor
2011. , s. 59
Serie
EN11
Nationell ämneskategori
Energiteknik
Identifikatorer
URN: urn:nbn:se:umu:diva-59082OAI: oai:DiVA.org:umu-59082DiVA, id: diva2:550871
Externt samarbete
Röbäcks Sweden AB
Utbildningsprogram
Högskoleingenjörsprogrammet i Energiteknik
Uppsök
teknik
Handledare
Examinatorer
Tillgänglig från: 2012-09-08 Skapad: 2012-09-08 Senast uppdaterad: 2012-09-08Bibliografiskt granskad

Open Access i DiVA

fulltext(2046 kB)1090 nedladdningar
Filinformation
Filnamn FULLTEXT01.pdfFilstorlek 2046 kBChecksumma SHA-512
31b94743c24f0c60464a6ab5b97b08b3bd383ed9187fee09112f3050b036b5bfd6b82e9ac3cedd3d6787318b0fdc4fd89ab176873cc9653d23ff75f63233cfc9
Typ fulltextMimetyp application/pdf

Av organisationen
Institutionen för tillämpad fysik och elektronik
Energiteknik

Sök vidare utanför DiVA

GoogleGoogle Scholar
Totalt: 1090 nedladdningar
Antalet nedladdningar är summan av nedladdningar för alla fulltexter. Det kan inkludera t.ex tidigare versioner som nu inte längre är tillgängliga.

urn-nbn

Altmetricpoäng

urn-nbn
Totalt: 260 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf