Assessment of horizontal laminar air flow instrument table for additional ultraclean space during surgery
Umeå University, Faculty of Medicine, Department of Surgical and Perioperative Sciences, Orthopaedics. (Ortopedi)ORCID iD: 0000-0002-8818-3408
Umeå University, Faculty of Medicine, Department of Clinical Microbiology.
Umeå University, Faculty of Medicine, Department of Surgical and Perioperative Sciences, Orthopaedics.
2010 (English)In: Journal of Hospital Infection, ISSN 0195-6701, E-ISSN 1532-2939, Vol. 76, no 3, 243-246 p.Article in journal (Refereed) Published
Abstract [en]

The area in a vertical ultraclean laminar air flow (LAF) theatre is usually too small to accommodate all the equipment needed for major surgery. We investigated the addition of an instrument table supplied with fixed ultraclean LAF and placed alongside the existing main LAF unit, to determine its physical and bacteriological effect on the main unit. In phase 1, with two investigators but without a patient, smoke tests showed no intrusion of air from the table into the main unit and particle counts did not show any adverse effect on the main LAF unit. In phase 2, during patients undergoing two total knee replacements, the LAF table and a table without LAF were placed alongside the main LAF unit. The tables were subjected to the activity of an extra operating room (OR) nurse working from inside the main LAF vigorously simulating handling of instruments. During this activity, the >5 μm particle counts were 275/m3 at the instrument table with LAF and 8550/m3 at the table without LAF (P < 0.0001). Also, without the OR nurse activity, the particle counts, just inside the main unit and adjacent to the LAF table, were significantly reduced (P < 0.03–0.003). Sedimentation plates on the LAF table and in the main unit registered 22 and 25 cfu/m2/h respectively compared with 45 cfu/m2/h at the instrument table without LAF. In conclusion, the results from the smoke tests, particle counts and bacteriological evaluation showed that the additional instrument table supplied with LAF is efficient and can be safely used as an extension additional to a main OR LAF unit.

Place, publisher, year, edition, pages
Elsevier , 2010. Vol. 76, no 3, 243-246 p.
Keyword [en]
Air contamination, Colony count, Laminar air flow, Operating room, Particle count
National Category
Medical and Health Sciences
URN: urn:nbn:se:umu:diva-37546DOI: 10.1016/j.jhin.2010.05.016ISI: 000282688700010OAI: diva2:361166
Available from: 2010-11-08 Created: 2010-11-08 Last updated: 2016-02-09Bibliographically approved

Open Access in DiVA

No full text

Other links

Publisher's full text

Search in DiVA

By author/editor
Nilsson, Kjell GLundholm, RolfFriberg, Sven
By organisation
OrthopaedicsDepartment of Clinical Microbiology
In the same journal
Journal of Hospital Infection
Medical and Health Sciences

Search outside of DiVA

GoogleGoogle Scholar
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Altmetric score

Total: 83 hits
ReferencesLink to record
Permanent link

Direct link